SIVACON 8PT

 
 
 

The Obvious Solution

For Global Challenges – SIVACON

Type testing in low-voltage switchgear is increasingly becoming an issue of prime importance worldwide. In future, there will be no other solution. But how far does one really have to go to a accomplish a type test? Often too far.

But that is now a thing of the past. With the “SIVACON Technology Partner concept, Siemens is bringing the versatile and type-tested SIVACON low voltage switchboard to your door.

To this end, Siemens has picked competent, local switchgear manufacturers and has appointed them SIVACON Technology Partners.

Your SIVACON Technology Partner will receive the concentrated know-how of Siemens at terms and conditions that only a local vendor is able to offer. For you, this means: SIVACON including type testing – faster, more flexibly and at lower cost than ever before.

Your advantage: “SIVACON Technology Partners”

These are qualified and permanently audited switchboard panel manufacturers, which Siemens has selected, close to you. This means that you always have the wealth of Siemens know-how at conditions that only a local supplier can offer. Fast, flexible and favorably priced.

As a power distribution board, SIVACON is available throughout the world and can be used at all power levels up to 7400 A, as withdrawable as well as plug-in and fixed-mounted units.

Always Flexible – SIVACON Adapts to your Requirements

Modular technology makes it possible to adapt SIVACON optimally to all requirements.

  • Standard horizontal busbar position at the top of the cubicle
  • Any components can be installed in the device compartments regardless of the busbar position and cubicle depth
  • Requirement-oriented compartmentalization of functional units (Form 1 to Form 4 according to IEC 60439-1)
  • Deep device compartments

Optimum Adaptation to Space Conditions

  • Wall-mounted or free-standing
  • Cables and busbars may be connected optionally from above or below
  • Cabling compartments front- or rear-located
  • Good accessibility of busbars

Technical Data at Galance
Standard and Specification Type-tested low-voltage switchgear IEC 60439-1, DIN EN 60439-1
and control gear assembly (TTA) (VDE 0660 Part 500)
Testing of response to internal faults IEC 61641, VDE 0660 Part 500, Supplement 2
(arcing faults)
Creepage distances and clearances Rated impulse withstand voltage (Uimp) 8 kV
Overvoltage category III
Pollution degree 3
Rated insulation voltage (Ui) 1000 V
Rated operational voltage (Ue) up to 690 V
Rated currents (In)Busbars (3-pole and 4-pole) Main horizontal busbars Rated current up to ≤ 7400 A
Rated peak withstand current (Ipk) up to ≤ 375 kA
Rated short-time withstand current (Icw) up to ≤ 150 kA, 1s
up to ≤ 120 kA, 3s
Vertical busbars for circuit breakers Rated current up to ≤ 6300 A
Rated peak withstand current (Ipk) up to ≤ 250 kA
Rated short-time withstand current (Icw) up to ≤ 100 kA, 1s
up to ≤ 80 kA, 3s
Vertical busbars for fixed-mounted design Rated current up to ≤ 1400 A
Rated peak withstand current (Ipk) up to ≤ 163 kA
Rated short-time withstand current (Icw) up to ≤ 65 kA*, 1s
up to ≤ 50 kA, 3s
Vertical busbars for in-line plug-in design (3NJ6) Rated current up to ≤ 2100 A
Rated peak withstand current (Ipk) up to ≤ 110 kA
Rated short-time withstand current (Icw) up to ≤ 50 kA*, 1s
Switchgear rated currents Circuit breakers up to 6300 A
Outgoing feeders up to 630 A
Internal separation Form 1 to Form 4 IEC 60439-1, Section 7.7, DIN EN 60439-1
Surface treatment Frame parts Galvanized/powder-coated/wet-painted
Enclosure Galvanized/powder-coated/wet-painted
Doors Powder-coated/wet-painted
Degree of protection To IEC 60529, EN 60529 IP 30 to IP 54
Dimensions Height: 2200, 2600 mm (with busbar top unit)
Width: 400, 600, 800, 1000, 1200 mm
Depth: 600, 800, 1000, 1200 mm
* Rated conditional short-circuit current Icc up to 100 kA